TRIO-PS-2G/3AC/24DC/5 - 29031538
|
TRIO-PS-2G/3AC/24DC/10 - 29031548
|
TRIO-PS-2G/3AC/24DC/20 - 29031558
|
TRIO-PS-2G/3AC/24DC/40 - 29031568
|
Environmental Product Compliance
|
China RoHS
|
Environmentally Friendly Use Period = 25;
|
Environmentally Friendly Use Period = 25;
|
Environmentally Friendly Use Period = 25;
|
Environmentally Friendly Use Period = 25;
|
REACH SVHC
|
|
|
Lead 7439-92-1
|
Lead 7439-92-1
|
General
|
Net weight
|
0.4 kg
|
0.9 kg
|
1.5 kg
|
2.6 kg
|
Efficiency
|
> 91 % (at 400 V AC and nominal values)
|
> 92 % (at 400 V AC and nominal values)
|
> 93 % (400 V AC)
|
typ. 93 % (400 V AC)
|
Insulation voltage input/output
|
3 kV AC (type test)
|
3 kV AC (type test)
|
3 kV AC (type test)
|
3 kV AC (type test)
|
|
1.5 kV AC (routine test)
|
1.5 kV AC (routine test)
|
1.5 kV AC (routine test)
|
1.5 kV AC (routine test)
|
Protection class
|
II (in closed control cabinet)
|
I (in closed control cabinet)
|
I (in closed control cabinet)
|
I (in closed control cabinet)
|
Degree of protection
|
IP20
|
IP20
|
IP20
|
IP20
|
MTBF (IEC 61709, SN 29500)
|
> 2300000 h (25 °C)
|
> 2100000 h (25 °C)
|
> 1800000 h (25 °C)
|
> 1730000 h (25 °C)
|
|
> 1300000 h (40 °C)
|
> 1200000 h (40 °C)
|
> 1100000 h (40 °C)
|
> 1051000 h (40 °C)
|
|
> 620000 h (60 °C)
|
> 590000 h (60 °C)
|
> 510000 h (60 °C)
|
> 510000 h (60 °C)
|
Mounting position
|
horizontal DIN rail NS 35, EN 60715
|
horizontal DIN rail NS 35, EN 60715
|
horizontal DIN rail NS 35, EN 60715
|
horizontal DIN rail NS 35, EN 60715
|
Assembly instructions
|
alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
|
alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
|
alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
|
alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
|
Efficiency
|
|
|
500 V AC
|
typ. 93.3 % (480 V AC)
|
Standards and Regulations
|
Electromagnetic compatibility
|
Conformance with EMC Directive 2014/30/EU
|
Conformance with EMC Directive 2014/30/EU
|
Conformance with EMC Directive 2014/30/EU
|
Conformance with EMC Directive 2014/30/EU
|
Noise emission
|
EN 55011 (EN 55022)
|
EN 55011 (EN 55022)
|
EN 55011 (EN 55022)
|
EN 55011 (EN 55022)
|
Noise immunity
|
Immunity according to EN 61000-6-2 (industrial)
|
Immunity according to EN 61000-6-2 (industrial)
|
Immunity according to EN 61000-6-2 (industrial)
|
Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial)
|
Standards/regulations
|
EN 61000-4-2
|
EN 61000-4-2
|
EN 61000-4-2
|
EN 61000-4-2
|
Contact discharge
|
4 kV (Test Level 2)
|
4 kV (Test Level 2)
|
4 kV (Test Level 2)
|
4 kV (Test Level 2)
|
Standards/regulations
|
EN 61000-4-3
|
EN 61000-4-3
|
EN 61000-4-3
|
EN 61000-4-3
|
Frequency range
|
80 MHz ... 1 GHz
|
80 MHz ... 1 GHz
|
80 MHz ... 1 GHz
|
80 MHz ... 1 GHz
|
Test field strength
|
10 V/m (Test Level 3)
|
10 V/m (Test Level 3)
|
10 V/m (Test Level 3)
|
10 V/m (Test Level 3)
|
Frequency range
|
1.4 GHz ... 2 GHz
|
1.4 GHz ... 2 GHz
|
1.4 GHz ... 2 GHz
|
1.4 GHz ... 2 GHz
|
Test field strength
|
3 V/m (Test Level 2)
|
3 V/m (Test Level 2)
|
3 V/m (Test Level 2)
|
3 V/m (Test Level 2)
|
Standards/regulations
|
EN 61000-4-4
|
EN 61000-4-4
|
EN 61000-4-4
|
EN 61000-4-4
|
Comments
|
Criterion B
|
Criterion B
|
Criterion B
|
Criterion B
|
Standards/regulations
|
EN 61000-6-3
|
EN 61000-6-3
|
EN 61000-6-3
|
EN 61000-6-3
|
|
EN 61000-4-6
|
EN 61000-4-6
|
EN 61000-4-6
|
EN 61000-4-6
|
Frequency range
|
0.15 MHz ... 80 MHz
|
0.15 MHz ... 80 MHz
|
0.15 MHz ... 80 MHz
|
0.15 MHz ... 80 MHz
|
Voltage
|
10 V (Test Level 3)
|
10 V (Test Level 3)
|
10 V (Test Level 3)
|
10 V (Test Level 3)
|
Conducted noise emission
|
EN 55016 EN 61000-6-4 (Class A)
|
EN 55016 EN 61000-6-4 (Class A)
|
EN 55016 EN 61000-6-4 (Class A)
|
EN 55016 EN 61000-6-4 (Class A)
|
Low Voltage Directive
|
Conformance with Low Voltage Directive 2014/35/EC
|
Conformance with Low Voltage Directive 2014/35/EC
|
Conformance with Low Voltage Directive 2014/35/EC
|
Conformance with Low Voltage Directive 2014/35/EC
|
Standard - Safety of transformers
|
EN 61558-2-16 (air clearances and creepage distances only)
|
EN 61558-2-16 (air clearances and creepage distances only)
|
EN 61558-2-16 (air clearances and creepage distances only)
|
|
Standard - Electrical safety
|
IEC 60950-1/VDE 0805 (SELV)
|
IEC 60950-1/VDE 0805 (SELV)
|
IEC 60950-1/VDE 0805 (SELV)
|
IEC 60950-1/VDE 0805 (SELV)
|
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
|
EN 50178/VDE 0160 (PELV)
|
EN 50178/VDE 0160 (PELV)
|
EN 50178/VDE 0160 (PELV)
|
EN 50178/VDE 0160 (PELV)
|
Standard – Safety extra-low voltage
|
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
|
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
|
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
|
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
|
Standard - Safe isolation
|
DIN VDE 0100-410
|
DIN VDE 0100-410
|
DIN VDE 0100-410
|
DIN VDE 0100-410
|
Standard – Limitation of mains harmonic currents
|
EN 61000-3-2
|
EN 61000-3-2
|
EN 61000-3-2
|
EN 61000-3-2
|
UL approvals
|
UL Listed UL 508
|
UL Listed UL 508
|
UL Listed UL 508
|
UL Listed UL 508
|
|
UL/C-UL Recognized UL 60950-1
|
UL/C-UL Recognized UL 60950-1
|
UL/C-UL Recognized UL 60950-1
|
UL/C-UL Recognized UL 60950-1
|
Shock
|
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
|
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
|
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
|
11 ms, 15g, in each space direction (according to IEC 60068-2-27)
|
Vibration (operation)
|
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
|
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
|
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
|
DNV GL CG-0339 / Class B
2 Hz - 100 Hz resonance search, 90 min. in resonance,
2 Hz - 13.2 Hz, ±1 mm amplitude,
13.2 Hz - 100 Hz, 0.7g acceleration
|
|
15 Hz ... 150 Hz, 4g, 90 min.
|
15 Hz ... 150 Hz, 4g, 90 min.
|
15 Hz ... 150 Hz, 4g, 90 min.
|
|
Rail applications
|
EN 50121-4
|
EN 50121-4
|
EN 50121-4
|
EN 50121-4
|
Shipbuilding approval
|
|
|
GL applied for
|
|
Standards/regulations
|
|
|
|
EN 61000-4-11
|
Overvoltage category (EN 60950-1)
|
|
|
|
II
|
Overvoltage category (EN 62477-1)
|
|
|
|
III
|
Connection data, input
|
Connection method
|
Push-in connection
|
Push-in connection
|
Push-in connection
|
Push-in connection
|
Conductor cross section solid min.
|
0.2 mm²
|
0.2 mm²
|
0.2 mm²
|
0.2 mm²
|
Conductor cross section solid max.
|
4 mm²
|
4 mm²
|
4 mm²
|
4 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
0.2 mm²
|
0.2 mm²
|
0.2 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
2.5 mm²
|
2.5 mm²
|
2.5 mm²
|
Conductor cross section AWG min.
|
24
|
24
|
24
|
24
|
Conductor cross section AWG max.
|
12
|
12
|
12
|
12
|
Stripping length
|
10 mm
|
10 mm
|
10 mm
|
10 mm
|
Output data
|
Nominal output voltage
|
24 V DC ±1 %
|
24 V DC ±1 %
|
24 V DC ±1 %
|
24 V DC ±1 %
|
Setting range of the output voltage (U
Set)
|
24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
|
24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
|
24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
|
24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
|
Nominal output current (I
N)
|
5 A
|
10 A
|
20 A
|
40 A
|
Dynamic Boost (I
Dyn.Boost)
|
7.5 A (5 s)
|
15 A (5 s)
|
30 A (5 s)
|
60 A (5 s)
|
Derating
|
> 60 °C ... 70 °C (2.5%/K)
|
> 60 °C ... 70 °C (2.5%/K)
|
> 60 °C ... 70 °C (2.5%/K)
|
> 60 °C ... 70 °C (2.5%/K)
|
Connection in parallel
|
Yes, for redundancy and increased capacity
|
Yes, for redundancy and increased capacity
|
Yes, for redundancy and increased capacity
|
Yes, for redundancy and increased capacity
|
Connection in series
|
yes
|
yes
|
yes
|
yes
|
Protection against surge voltage on the output
|
≤ 30 V DC
|
≤ 30 V DC
|
≤ 30 V DC
|
≤ 30 V DC
|
Control deviation
|
< 1 % (change in load, static 10 % ... 90 %)
|
< 1 % (change in load, static 10 % ... 90 %)
|
< 1 % (change in load, static 10 % ... 90 %)
|
< 1 % (change in load, static 10 % ... 90 %)
|
|
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
|
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
|
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
|
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
|
|
< 0.1 % (change in input voltage ±10 %)
|
< 0.1 % (change in input voltage ±10 %)
|
< 0.1 % (change in input voltage ±10 %)
|
< 0.1 % (change in input voltage ±10 %)
|
Residual ripple
|
≤ 20 mV
PP
|
≤ 20 mV
PP
|
≤ 20 mV
PP
|
≤ 50 mV
PP
|
Output power
|
120 W
|
240 W
|
480 W
|
960 W
|
Typical response time
|
< 1 s
|
< 1 s
|
< 1 s
|
< 1 s
|
Maximum power dissipation in no-load condition
|
< 1 W (400 V AC)
|
< 1.1 W (400 V AC)
|
< 1.2 W (400 V AC)
|
< 14 W (400 V AC)
|
Power loss nominal load max.
|
< 12 W (480 V AC)
|
< 22 W (480 V AC)
|
< 38 W (480 V AC)
|
< 68 W (480 V AC)
|
Feedback resistance
|
|
|
|
< 35 V
|
Short-circuit current
|
|
|
|
< (Permanent)
|
Connection data for signaling
|
Connection method
|
Push-in connection
|
Push-in connection
|
Push-in connection
|
Push-in connection
|
Conductor cross section solid min.
|
0.2 mm²
|
0.2 mm²
|
0.2 mm²
|
0.2 mm²
|
Conductor cross section solid max.
|
1.5 mm²
|
1.5 mm²
|
1.5 mm²
|
1.5 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
0.2 mm²
|
0.2 mm²
|
0.2 mm²
|
Conductor cross section flexible max.
|
1.5 mm²
|
1.5 mm²
|
1.5 mm²
|
1.5 mm²
|
Conductor cross section AWG min.
|
24
|
24
|
24
|
24
|
Conductor cross section AWG max.
|
16
|
16
|
16
|
16
|
Stripping length
|
8 mm
|
8 mm
|
8 mm
|
8 mm
|
Dimensions
|
Width
|
35 mm
|
42 mm
|
65 mm
|
110 mm
|
Height
|
130 mm
|
130 mm
|
130 mm
|
130 mm
|
Depth
|
115 mm
|
160 mm
|
160 mm
|
160 mm
|
Weight per piece
|
568.5 GRM
|
1070.0 GRM
|
1717.0 GRM
|
2850.0 GRM
|
Input data
|
Nominal input voltage range
|
3x 400 V AC ... 500 V AC
|
3x 400 V AC ... 500 V AC
|
3x 400 V AC ... 500 V AC
|
3x 400 V AC ... 500 V AC
|
|
2x 400 V AC ... 500 V AC
|
2x 400 V AC ... 500 V AC
|
2x 400 V AC ... 500 V AC
|
|
Input voltage range
|
3x 400 V AC ... 500 V AC -20 % ....+15 %
|
3x 400 V AC ... 500 V AC -20 % ....+15 %
|
3x 400 V AC ... 500 V AC -20 % ....+15 %
|
3x 400 V AC ... 500 V AC -20 % ....+15 %
|
|
2x 400 V AC ... 500 V AC -10 % ... +15 %
|
2x 400 V AC ... 500 V AC -10 % ... +15 %
|
2x 400 V AC ... 500 V AC -10 % ... +15 %
|
|
AC frequency range
|
50 Hz ... 60 Hz
|
50 Hz ... 60 Hz
|
50 Hz ... 60 Hz
|
50 Hz ... 60 Hz
|
Discharge current to PE
|
< 0.25 mA
|
< 3.5 mA
|
< 3.5 mA
|
< 3.5 mA
|
Current consumption
|
3x 0.4 A (400 V AC)
|
3x 0.6 A (400 V AC)
|
3x 1.2 A (400 V AC)
|
3x 1.9 A (400 V AC)
|
|
3x 0.3 A (500 V AC)
|
3x 0.6 A (500 V AC)
|
3x 1 A (500 V AC)
|
3x 1.7 A (500 V AC)
|
|
2x 0.6 A (400 V AC)
|
2x 1.1 A (400 V AC)
|
2x 2.3 A (400 V AC)
|
|
|
2x 0.5 A (500 V AC)
|
2x 1.1 A (500 V AC)
|
2x 1.9 A (500 V AC)
|
|
Nominal power consumption
|
243.6 VA
|
451.7 VA
|
822.2 VA
|
1335.1 VA
|
Inrush surge current
|
≤ 22 A (typical)
|
≤ 26 A (typical)
|
≤ 22 A (typical)
|
≤ (typical)
|
Mains buffering
|
typ. 20 ms (400 V AC)
|
typ. 10 ms (400 V AC)
|
typ. 10 ms (400 V AC)
|
typ. 10 ms (400 V AC)
|
|
typ. 20 ms (500 V AC)
|
typ. 20 ms (500 V AC)
|
typ. 20 ms (500 V AC)
|
typ. 20 ms (500 V AC)
|
Input fuse
|
3.15 A (internal (device protection), slow-blow)
|
3.15 A (internal (device protection), slow-blow)
|
3.15 A (internal (device protection), slow-blow)
|
6.3 A (internal (device protection))
|
Choice of suitable circuit breakers
|
6 A ... 16 A (Characteristics B, C, D, K)
|
6 A ... 16 A (Characteristics B, C, D, K)
|
6 A ... 16 A (Characteristics B, C, D, K)
|
10 A ... 16 A (Characteristics B, C, D, K)
|
Power factor (cos phi)
|
0.55
|
0.58
|
0.63
|
0.77
|
Type of protection
|
Transient surge protection
|
Transient surge protection
|
Transient surge protection
|
Transient surge protection
|
Protective circuit/component
|
Varistor
|
Varistor
|
Varistor
|
Varistor
|
Connection data, output
|
Connection method
|
Push-in connection
|
Push-in connection
|
Push-in connection
|
Push-in connection
|
Conductor cross section solid min.
|
0.2 mm²
|
0.2 mm²
|
0.2 mm²
|
0.75 mm²
|
Conductor cross section solid max.
|
4 mm²
|
4 mm²
|
10 mm²
|
16 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
0.2 mm²
|
0.2 mm²
|
0.75 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
2.5 mm²
|
6 mm²
|
10 mm²
|
Conductor cross section AWG min.
|
24
|
24
|
24
|
20
|
Conductor cross section AWG max.
|
12
|
12
|
8
|
4
|
Stripping length
|
10 mm
|
10 mm
|
15 mm
|
18 mm
|
Ambient conditions
|
Degree of protection
|
IP20
|
IP20
|
IP20
|
IP20
|
Ambient temperature (operation)
|
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
|
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
|
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
|
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
|
Ambient temperature (storage/transport)
|
-40 °C ... 85 °C
|
-40 °C ... 85 °C
|
-40 °C ... 85 °C
|
-40 °C ... 85 °C
|
Max. permissible relative humidity (operation)
|
≤ 95 % (at 25 °C, non-condensing)
|
≤ 95 % (at 25 °C, non-condensing)
|
≤ 95 % (at 25 °C, non-condensing)
|
≤ 95 % (at 25 °C, non-condensing)
|
Climatic class
|
3K3 (in acc. with EN 60721)
|
3K3 (in acc. with EN 60721)
|
3K3 (in acc. with EN 60721)
|
3K3 (in acc. with EN 60721)
|
Degree of pollution
|
2
|
2
|
2
|
2
|
Installation height
|
≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
|
≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
|
≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
|
≤ 4000 m (> 2000 m, Derating: 10 %/1000 m)
|
Ambient temperature (start-up type tested)
|
|
-40 °C
|
-40 °C
|
-40 °C
|
Approvals
|
|
- DNV GL
- cULus Listed
- cULus Recognized
- EAC
- UL Recognized
- cUL Recognized
- cUL Listed
- IECEE CB Scheme
- UL Listed
|