85M-1602-T Specifications
|
• Inputs and Outputs
|
Digital Inputs
|
16 channels
|
Isolation
|
3k VDC or 2k Vrms
|
• Digital Input
|
Sensor Type
|
Wet contact (NPN or PNP), dry contact
|
I/O Mode
|
DI, Counter or Frequncy
|
Dry Contact
|
• On: short to GND
• Off: open
|
Wet Contact (DI to COM)
|
• Off: 0 to 3 VDC
• On: 10 to 30 VDC
|
Common Type
|
8 points per COM
|
Counter Frequency
|
5 kHz
|
Digital Filtering Time Interval
|
Software selectable (by 0.1 ms)
|
• Physical Characteristics
|
Wiring
|
I/O cable, 16 AWG (max.)
|
Connector
|
Spring-type terminal block
|
• Environmental Limits
|
Operating Temperature
|
-40 to 75°C (-40 to 176°F)
|
• Power Requirements
|
Input Current
|
363.6 mA @ 3.3 VDC
|
• MTBF (mean time between failures)
|
Time
|
1,132,561 hrs
|
Standard
|
Telcordia SR332
|
|
85M-2600-T Specifications
|
• Inputs and Outputs
|
Digital Outputs
|
16 channels
|
Isolation
|
3k VDC or 2k Vrms
|
• Digital Output
|
Type
|
Sink
|
I/O Mode
|
DO or PWM
|
Pulse Output Frequency
|
5 kHz
|
Over-Voltage Protection
|
45 VDC
|
Over-Current Protection
|
2.6 A (4 channels @ 650 mA)
|
Over-Temperature Shutdown
|
175°C (typical), 150°C (min.)
|
Current Rating
|
200 mA per channel
|
• Physical Characteristics
|
Wiring
|
I/O cable, 16 AWG (max.)
|
Connector
|
Spring-type terminal block
|
• Environmental Limits
|
Operating Temperature
|
-40 to 75°C (-40 to 176°F)
|
• Power Requirements
|
Input Current
|
257.6 mA @ 3.3 VDC
|
• MTBF (mean time between failures)
|
Time
|
792,571 hrs
|
Standard
|
Telcordia SR332
|
|
85M-3800-T Specifications
|
• Inputs and Outputs
|
Analog Inputs
|
8 channels
|
Isolation
|
3k VDC or 2k Vrms
|
• Analog Input
|
Type
|
Differential
|
Resolution
|
16 bits
|
I/O Mode
|
4 to 20 mA (wire off)
|
Accuracy
|
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
|
Sampling Rate
|
• All channels: 100 samples/sec
• Per channel: 12.5 samples/sec
|
Input Impedance
|
125 ohms (min.)
|
• Physical Characteristics
|
Wiring
|
I/O cable, 16 AWG (max.)
|
Connector
|
Spring-type terminal block
|
• Environmental Limits
|
Operating Temperature
|
-40 to 75°C (-40 to 176°F)
|
• Power Requirements
|
Input Current
|
318.2 mA @ 3.3 VDC
|
• MTBF (mean time between failures)
|
Time
|
1,512,906 hrs
|
Standard
|
Telcordia SR332
|
|
85M-3810-T Specifications
|
• Inputs and Outputs
|
Analog Inputs
|
8 channels
|
Isolation
|
3k VDC or 2k Vrms
|
• Analog Inputs
|
Type
|
Differential
|
Resolution
|
16 bits
|
I/O Mode
|
0 to 10 VDC
|
Accuracy
|
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
|
Sampling Rate
|
• All channels: 100 samples/sec
• Per channel: 12.5 samples/sec
|
Input Impedance
|
200 kilo-ohms (min.)
|
• Physical Characteristics
|
Wiring
|
I/O cable, 16 AWG (max.)
|
Connector
|
Spring-type terminal block
|
• Environmental Limits
|
Operating Temperature
|
-40 to 75°C (-40 to 176°F)
|
• Power Requirements
|
Input Current
|
315.2 mA @ 3.3 VDC
|
• MTBF (mean time between failures)
|
Time
|
1,530,690 hrs
|
Standard
|
Telcordia SR332
|
|
85M-3801-T Specifications
|
• Inputs and Outputs
|
Analog Inputs
|
8 channels
|
Isolation
|
3k VDC or 2k Vrms
|
• Analog Input
|
Type
|
Differential
|
Resolution
|
16 bits
|
I/O Mode
|
4 to 20 mA (wire off)
|
Historical Data Buffering
|
60 KB per channel, 6-second data buffer at 5 kHz
|
Accuracy
|
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
|
Sampling Rate
|
• All channels: 40k samples/sec
• Per channel: 5k samples/sec
|
Input Impedance
|
125 ohms (min.)
|
• Physical Characteristics
|
Wiring
|
I/O cable, 16 AWG (max.)
|
Connector
|
Spring-type terminal block
|
• Environmental Limits
|
Operating Temperature
|
-40 to 75°C (-40 to 176°F)
|
• Power Requirements
|
Input Current
|
378.8 mA @ 3.3 VDC
|
• MTBF (mean time between failures)
|
Time
|
1,426,112 hrs
|
Standard
|
Telcordia SR332
|
|
85M-3811-T Specifications
|
• Inputs and Outputs
|
Analog Inputs
|
8 channels
|
Isolation
|
3k VDC or 2k Vrms
|
• Analog Inputs
|
Type
|
Differential
|
Resolution
|
16 bits
|
I/O Mode
|
0 to 10 VDC
|
Historical Data Buffering
|
60 KB per channel, 6-second data buffer at 5 kHz
|
Accuracy
|
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
|
Sampling Rate
|
• All channels: 40k samples/sec
• Per channel: 5k samples/sec
|
Input Impedance
|
20 mega-ohms (min.)
|
• Physical Characteristics
|
Wiring
|
I/O cable, 16 AWG (max.)
|
Connector
|
Spring-type terminal block
|
• Environmental Limits
|
Operating Temperature
|
-40 to 75°C (-40 to 176°F)
|
• Power Requirements
|
Input Current
|
378.8 mA @ 3.3 VDC
|
• MTBF (mean time between failures)
|
Time
|
1,426,112 hrs
|
Standard
|
Telcordia SR332
|
|
85M-6600-T Specifications
|
• Inputs and Outputs
|
RTD Inputs
|
6 channels
|
Isolation
|
3k VDC or 2k Vrms
|
• RTDs
|
Input Type
|
• PT50, PT100, PT200, PT500 (-200 to 850°C)
• PT1000 (-200 to 350°C) • JPT100, JPT200, JPT500 (-200 to 640°C) • JPT1000 (-200 to 350°C) • NI100, NI200, NI500 (-60 to 250°C) • NI1000 (-60 to 150°C) • NI120 (-80 to 260°C) • Resistance of 310, 620
|
Sampling Rate (single channel)
|
• All channels: 12 samples/sec
• Per channel: 2 samples/sec
|
Resolution
|
0.1°C or 0.1 ohms
|
Accuracy
|
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
|
Input Impedance
|
625 kilo-ohms (min.)
|
Wiring
|
I/O cable, 16 AWG (max.)
|
Connector
|
Spring-type terminal block
|
• Environmental Limits
|
Operating Temperature
|
-40 to 75°C (-40 to 176°F)
|
• Power Requirements
|
Input Current
|
201.5 mA @ 3.3 VDC
|
• MTBF (mean time between failures)
|
Time
|
571,446 hrs
|
Standard
|
Telcordia SR332
|
|
85M-6810-T Specifications
|
• Inputs and Outputs
|
Analog Inputs
|
8 channels
|
Isolation
|
3k VDC or 2k Vrms
|
• Thermocouples
|
Sensor Type
|
J (0 to 750°C), K (-200 to 1250°C), T (-200 to 350°C), E (-200 to 900°C), R (-50 to 1600°C), S (-50 to 1760°C), B (600 to 1700°C), N (-200 to 1300°C)
|
Millivolt Type
|
• Mode: ±78.126 mV, ±39.062 mV, ±19.532 mV
• Fault and over-voltage protection: -35 to +35 VDC (power off); -25 to +30 VDC (power on)
|
Sampling Rate (single channel)
|
• All channels: 12 samples/sec
• Per channel: 1.5 samples/sec
|
Resolution
|
16 bits
|
Accuracy
|
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
|
Input Impedance
|
1 mega-ohm (min.)
|
Wiring
|
I/O cable, 16 AWG (max.)
|
Connector
|
Spring-type terminal block
|
• Environmental Limits
|
Operating Temperature
|
-40 to 75°C (-40 to 176°F)
|
• Power Requirements
|
Input Current
|
175.5 mA @ 3.3 VDC
|
• MTBF (mean time between failures)
|
Time
|
2,324,891 hrs
|
Standard
|
Telcordia SR332
|
|
85M-5401-T Specifications
|
• Serial Communication
|
Interface
|
4 RS-232/422/485 ports, software selectable (DB44 female)
|
Isolation
|
3k VDC or 2k Vrms
Note: DB44 to 4-port DB9 cable included in the package.
|
• Serial Communication Parameters
|
Parity
|
None, Even, Odd
|
Data Bits
|
7, 8
|
Stop Bits
|
1, 2
|
Flow Control
|
RTS/CTS, XON/XOFF
|
Baudrate
|
300 bps to 921.6 kbps
|
• Serial Signals
|
RS-232
|
TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
|
RS-422
|
Tx+, Tx-, Rx+, Rx-, GND
|
RS-485-4w
|
Tx+, Tx-, Rx+, Rx-, GND
|
RS-485-2w
|
Data+, Data-, GND
|
• Physical Characteristics
|
Connector
|
DB44 female
|
• Environmental Limits
|
Operating Temperature
|
-40 to 75°C (-40 to 176°F)
|
• Power Requirements
|
Input Current
|
375.8 mA @ 3.3 VDC
|
• MTBF (mean time between failures)
|
Time
|
596,611 hrs
|
Standard
|
Telcordia SR332
|
|
Common Specifications
|
• Power Requirements
|
Input Voltage
|
24 VDC (9 to 48 VDC)
|
• Environmental Limits
|
Storage Temperature
|
-40 to 85°C (-40 to 185°F)
|
Ambient Relative Humidity
|
5 to 95% (non-condensing)
|
Shock
|
IEC 60068-2-27
|
Vibration
|
IEC 60068-2-6
|
• Standards and Certifications
|
Safety
|
UL 508
|
EMC
|
EN 55032/24
|
EMI
|
FCC Part 15 Subpart B Class A, CISPR 32
|
EMS
|
IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1000 MHz: 3 V/m 1400 MHz to 2100 MHz: 3 V/m 2100 MHz to 2700 MHz: 1 V/m IEC 61000-4-4 EFT: Power: 1 kV; Signal 0.5 kV IEC 61000-4-5 Surge: Power: 2 kV (L-PE), 1 kV (L-L);
|
Rail Traffic
|
EN 50155*, EN 50121-3-2, EN 50121-4
*Complies with a portion of EN 50155 specifications.
|
• Warranty
|
Warranty Period
|
5 years
|
Details
|
See www.moxa.com/warranty
|