Three-Way Communication
The ICF-1150 series support 2 serial ports, with a D-sub connector
for RS-232 communication and a removable terminal block for RS-422 or
RS-485 communication. The 3 ports (2 serial ports and one fiber port)
are completely independent. When an ICF-1150 converter receives data
from any one port, it will send the data out through the other 2 ports.
For example, once the ICF-1150 converter receives a command from the
remote master through the fiber port, it will convert the signal and
send the command through the RS-232 and RS-422/485 ports at the same
time. If the user is monitoring a system running on an RS-485 network,
there is no need to use an additional RS-232 to RS-485 converter to
connect the laptop computer's serial port to the RS-485 bus.
Rotary Switch for Setting the Pull High/Low Resistor
The RS-485 interface supports multi-drop or daisy-chain connections,
which system engineers will use to connect serial devices such as
meters, RTUs, and readers together on the same bus. Since the number of
serial devices on the same bus will cause the impedance of the data
line to increase, the ICF-1150 allows users to tune the pull high/low
resistor. Just rotate the switch to the appropriate value without
removing the ICF-1150 from the DIN-rail.
Optical Fiber Side
|
Fiber Connector
|
SC or ST
|
Cable Requirements
|
Single-mode: 8.3/125, 8.7/125, 9/125, or 10/125 μm
Multi-mode: 50/125, 62.5/125, or 100/140 μm
|
Transmission Distance
|
Single-mode: 40 km
Multi-mode: 5 km
|
Wavelength
|
ICF-1150-S (single-mode): 1310 nm
ICF-1150-M (multi-mode): 850 nm
|
Tx Output
|
ICF-1150-S (single-mode): > -5 dBm
ICF-1150-M (multi-mode): > -5 dBm
|
Rx Sensitivity
|
ICF-1150-S (single-mode): -25 dBm
ICF-1150-M (multi-mode): -20 dBm
|
Point-to-Point Transmission
|
Half-duplex or full-duplex
|
Ring Transmission
|
Half-duplex
|
• RS-232/422/485 Side
|
RS-232 Signals
|
TxD, RxD, GND
|
RS-422 Signals
|
TxD+, TxD-, RxD+, RxD-, GND
|
RS-485-4w Signals
|
TxD+, TxD-, RxD+, RxD-, GND
|
RS-485-2w Signals
|
Data+, Data-, GND
|
Baudrate
|
50 bps to 921.6 Kbps
|
ESD Protection
|
15 KV for all signals
|
Isolation
|
2 KV RMS isolation per I/O port for 1 minute
|
• Physical Characteristics
|
Housing
|
Aluminum (1 mm)
|
Dimensions
|
30.3 x 70 x 115 mm (1.19 x 2.76 x 4.53 in)
|
Weight
|
330 g
|
• Environmental Limits
|
Operating Temperature
|
Standard Models: 0 to 60°C (32 to 140°F)
Wide Temp. Models: -40 to 85°C (-40 to 185°F)
|
Storage Temperature
|
-40 to 85°C (-40 to 185°F)
|
Ambient Relative Humidity
|
5 to 95% (non-condensing)
|
• Power Requirements
|
Input Voltage
|
12 to 48 VDC
|
Power Consumption
|
ICF-1150: 127 mA @ 12 V
ICF-1150I: 163 mA @ 12 V
|
Voltage Reversal Protection
|
Protects against V+/V- reversal
|
Over Current Protection
|
1.1 A (protects against two signals shorted together)
|
• Standards and Certifications
|
Safety
|
UL 508
|
Hazardous Location
|
UL/cUL Class I Division 2 Groups A/B/C/D, ATEX Zone 2 EEx nC IIC
|
EMC
|
CE, FCC
|
EMI
|
EN 55022 Class B, FCC Part 15 Subpart B Class B
|
EMS
|
EN 61000-4-2 (ESD) Level 4,
EN 61000-4-3 (RS) Level 2,
EN 61000-4-4 (EFT) Level 4,
EN 61000-4-5 (Surge) Level 3,
EN 61000-4-6 (CS) Level 2,
EN 61000-4-8 (PFMF) Level 3
|
Freefall
|
IEC 60068-2-32
|
Green Product
|
RoHS, CRoHS, WEEE
|
• MTBF (mean time between failures)
|
Time
|
792,085 hrs
|
Database
|
Telcordia (Bellcore), GB
|
Water and Dust Proof
|
IP30
|
• Warranty
|
Warranty Period
|
5 years
|
Dimensions
|
|
|
|
|
|
|