• Inputs and Outputs |
Digital Inputs |
8 channels |
Configurable DIOs |
8 channels |
• Digital Input |
Sensor Type |
Wet Contact (NPN or PNP), Dry Contact |
I/O Mode |
DI or Event Counter |
Dry Contact |
• On: short to GND
• Off: open
|
Wet Contact |
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
|
Isolation |
3K VDC or 2K Vrms |
Counter Frequency |
250 Hz, power off storage |
• Digital Output |
Type |
Sink |
I/O Mode |
DO or Pulse Output |
Pulse Output Frequency |
500 Hz |
Over-voltage Protection |
45 VDC |
Over-current Protection |
2.6 A (4 channels @ 650 mA) |
Over-temperature Shutdown |
175°C (typical), 150°C (min.) |
Current Rating |
200 mA per channel |
Isolation |
3K VDC or 2K Vrms |
• LAN |
Ethernet |
2 x 10/100 Mbps switch ports, RJ45 |
Protection |
1.5 KV magnetic isolation |
Protocols |
Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, HTTP |
• Power Requirements |
Power Input |
24 VDC nominal, 12 to 36 VDC |
Power Consumption |
155 mA @ 24 VDC |
• Physical Characteristics |
Wiring |
I/O cable max. 14 AWG |
Dimensions |
27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in) |
Weight |
under 200 g |
• Environmental Limits |
Operating Temperature |
Standard Model: -10 to 60°C (14 to 140°F) Wide Temp. Model: -40 to 75°C (-40 to 167°F) |
Storage Temperature |
-40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity |
5 to 95% (non-condensing) |
• Standards and Certifications |
Safety |
UL 508 |
EMI |
FCC Part 15 Subpart B Class A |
EMS |
IEC 61000-4, IEC 61000-6 |
Shock |
IEC 60068-2-27 |
Freefall |
IEC 60068-2-32 |
Vibration |
IEC 60068-2-6 |
• MTBF (mean time between failures) |
Time |
179,098 hrs |
Database |
Telcordia (Bellcore) |
• Warranty |
Warranty Period |
5 years |