The MGate 5114 is an industrial Ethernet gateway with 2 Ethernet ports and 1 RS-232/422/485 serial port for Modbus RTU/ASCII/TCP, IEC 60870-5-101, and IEC 60870-5-104 network communications. By integrating commonly used power protocols, the MGate 5114 provides the flexibility needed to fulfill the various conditions that arise with field devices that use different communications protocols to connect to a power SCADA system. To integrate Modbus or IEC 60870-5-101 devices onto an IEC 60870-5-104 network, use the MGate 5114 as a Modbus master/client or IEC 60870-5-101 master to collect data and exchange data with IEC 60870-5-104 systems.
• Industrial Protocols
|
Protocols
|
SAE J1939, Modbus RTU/ASCII/TCP, PROFINET, EtherNet/IP
|
Protocol Conversion
|
• J1939 to Modbus RTU/ASCII (Master/Slave)
• J1939 to Modbus TCP (Client/Server) • J1939 to EtherNet/IP (Scanner/Adapter) • J1939 to PROFINET (I/O Device)
|
• Ethernet Interface
|
Protocols
|
Modbus TCP (Client/Server), PROFINET (I/O device), EtherNet/IP (Scanner/Adapter)
|
Number of Ports
|
2 (1 IP address, supports Ethernet cascading)
|
Speed
|
10/100 Mbps, Auto MDI/MDIX
|
Connector
|
8-pin RJ45
|
Magnetic Isolation Protection
|
1.5 kV (built-in)
|
• CAN-J1939 Serial Interface
|
Protocols
|
SAE J1939
|
Number of Ports
|
1
|
Connectors
|
6-pin terminal block
|
Terminator
|
120 Ω
|
Isolation
|
2 kv (built-in)
|
Data Rate
|
250 kbps and 500 kbps
|
• Modbus Serial Interface
|
Protocols
|
Modbus RTU/ASCII (Master/Slave)
|
Number of Ports
|
1
|
Serial Standards
|
RS-232/422/485, software selectable
|
Connectors
|
DB9 male
|
Pull High/Low Resistor for RS-485
|
1 kΩ, 150 kΩ
|
Terminator for RS-485
|
120 Ω
|
Isolation
|
2 kV (built-in)
|
• Modbus Serial Communication Parameters
|
Data Bits
|
8
|
Stop Bits
|
1, 2
|
Parity
|
None, Even, Odd, Space, Mark
|
Flow Control
|
RTS/CTS, RTS Toggle
|
Baudrate
|
50 bps to 921.6 kbps
|
• Modbus Serial Signals
|
RS-232
|
TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
|
RS-422
|
Tx+, Tx-, Rx+, Rx-, GND
|
RS-485-4w
|
Tx+, Tx-, Rx+, Rx-, GND
|
RS-485-2w
|
Data+, Data-, GND
|
• Software
|
Configuration Options
|
Web console
|
Utility
|
Device Search Utility (DSU) for Windows 95, 98, ME, NT, 2000, Windows XP, Server 2003, Vista, Server 2008 (x86/x64), Windows Server 2008 R2, Windows 7/8/8.1/10 (x86/x64), Windows Server 2012 (x64), Windows 2012 R2
|
Network Protocols
|
TCP/IP, UDP, HTTP, SMTP, NTP, DNS, DHCP Client, SNMP (v1, v2, v3), MIB-II, ARP, Telnet
|
Support
|
MXview, MXconfig, IEC 62443-4-2
|
• Physical Characteristics
|
Housing
|
Metal, IP30
|
Weight
|
589 g (1.30 lb)
|
Dimensions
|
45.8 x 105 x 134 mm (1.8 x 4.13 x 5.28 in)
|
• Environmental Limits
|
Operating Temperature
|
Standard Models: 0 to 60°C (32 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
|
Storage Temperature
|
-40 to 85°C (-40 to 185°F)
|
Ambient Relative Humidity
|
5 to 95% (non-condensing)
|
Vibration
|
IEC 60068-2-6, IEC 60068-2-64
|
Shock
|
IEC 60068-2-27
|
Drop
|
IEC 60068-2-32
|
• Power Requirements
|
Input Voltage
|
12 to 48 VDC
|
Input Current
|
• 416 mA @ 12 VDC
• 195 mA @ 24 VDC; • 110 mA @ 48 VDC
|
Power Connector
|
Terminal block
|
• Standards and Certifications
|
Safety
|
EN 60950-1(LVD), UL 61010-2-201
|
Hazardous Location
|
Class I Division 2, ATEX, IECEx (Note: Certification is underway. Please contact a Moxa slaes representative for details.)
|
EMC
|
EN 61000-6-2/6-4
|
EMI
|
CISPR 22, FCC Part 15B Class B
|
EMS
|
IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV IEC 61000-4-5 Surge: Power 1 kV; Signal: 1 kV IEC 61000-4-6 CS: 10 V IEC 61000-4-8 PFMF: 10 A/m
|
• Reliability
|
Alarm Functions
|
Relay, email, SNMP trap
|
Alert Tools
|
Built-in buzzer
|
Storage Card Slot
|
1 microSD (SDHC) card slot; supports up to 32 GB
|
• MTBF (mean time between failures)
|
Time
|
727,873 hrs
|
Standard
|
Telcordia SR332
|
• Warranty
|
Warranty Period
|
5 years
|
Details
|
See www.moxa.com/warranty
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Features
- Key-in-free J1939 command auto detection
- Built-in J1939 traffic monitoring/diagnostics/live-list tools
- Supports J1939 to Modbus RTU/ASCII/TCP, EtherNet/IP, PROFINET protocol conversion
- Ready for hazardous locations: C1D2, ATEX, IECEx
- MicroSD card for configuration backup/duplication, and event log
- 2 kV CANbus and Modbus serial port isolation
- -40 to 75°C wide operating temperature models available
- Security features based on IEC 62443
|
|
|
|
|
|
|