The MGate MB3170 and MB3270 are 1 and 2-port Modbus gateways, respectively, that convert between Modbus TCP, ASCII, and RTU communication protocols. The gateways provide both serial-to-Ethernet communication and serial(Master)-to-serial(Slave) communication. In addition, the gateways support simultaneously connecting serial and Ethernet masters with serial Modbus devices. The MGate MB3170 and MB3270 series gateways can be accessed by up to 16 TCP master/clients or connect to up to 32 TCP slave/servers. Routing through the serial ports can be controlled by IP address, TCP port number, or ID mapping. A featured priority control function allows urgent commands to obtain an immediate response. All models are rugged, DIN-rail mountable, and offer optional built-in optical isolation for serial signals.
Integration of TCP masters without alteration to Modbus RTU/ASCII network or software
The MB3270 can integrate Modbus TCP with Modbus RTU/ASCII, without modifying the existing Modbus RTU/ASCII architecture or software. With the serial redirector function, a serial master can maintain direct access to serial slave devices through a specially mapped serial port. This allows the serial and TCP masters to access serial slaves simultaneously. Cascading Ethernet ports for easy wiring
Advanced models of the MGate™ MB3000 series have two Ethernet ports to make network wiring easier. Dual Ethernet ports allow users to string multiple Modbus gateways together using standard RJ45 Ethernet cables, eliminating the need for a separate Ethernet switch.
Redundant power inputs
Advanced models of the MB3000 series have dual power inputs for greater reliability. The power inputs allow simultaneous connections to two live DC power sources, so that continuous operation is provided even if one power source fails. The higher level of reliability makes these advanced Modbus gateways ideal for demanding industrial applications. Warning by relay output
A relay output is provided for the Ethernet link and power input status. The relay output gives maintenance engineers an additional tool for troubleshooting and maintenance. Priority control for urgent commands (Patented)
As Modbus networks increase in size and complexity, the lag time between commands and responses becomes a major concern. Advanced models of the MB3000 series provide a priority control function for urgent commands, allowing users to force certain commands to get an immediate response. Depending on your system’s requirements, different methods are available to define which commands receive priority.
• Ethernet Interface
|
Protocol
|
Modbus TCP
|
Number of Ports
|
2 (1 IP, Ethernet cascade)
|
Speed
|
10/100 Mbps, Auto MDI/MDIX
|
Connector
|
8-pin RJ45
|
Magnetic Isolation Protection
|
1.5 kV (built-in)
|
• Optical Fiber Interface
|
Table
|
|
• Serial Interface
|
Protocol
|
Modbus RTU/ASCII Slave/Master
|
Number of Ports
|
MB3170/3170I: 1
MB3270/3270I: 2
|
Serial Standards
|
RS-232/422/485, software selectable
|
Connectors
|
MB3170/3170I: DB9 male for RS-232, terminal block for RS-422/485
MB3270/3270I: DB9 male x 2
|
Magnetic Isolation Protection
|
2 kV (for “I” models)
|
ESD Protection
|
15 kV for all signals
|
RS-485 Data Direction Control
|
ADDC® (automatic data direction control)
|
Pull High/Low Resistor for RS-485
|
1 kΩ, 150 kΩ
|
Terminator for RS-485
|
120 Ω
|
• Serial Communication Parameters
|
Data Bits
|
8
|
Stop Bits
|
1, 2
|
Parity
|
None, Even, Odd, Space, Mark
|
Flow Control
|
RTS/CTS, DTR/DSR, RTS Toggle (RS-232 only)
|
Baudrate
|
50 bps to 921.6 kbps
|
• Serial Signals
|
RS-232
|
TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
|
RS-422
|
Tx+, Tx-, Rx+, Rx-, GND
|
RS-485-4w
|
Tx+, Tx-, Rx+, Rx-, GND
|
RS-485-2w
|
Data+, Data-, GND
|
• Software
|
Configuration Options
|
Web Console, Serial Console, Telnet Console, Windows Utility
|
Utility
|
MGate Manager for Windows 95, 98, ME, NT, 2000, Windows XP, Server 2003, Vista, Server 2008 (x86/x64), Windows Server 2008 R2, Windows 7/8/8.1 (x86/x64), Windows Server 2012 (x64), Windows 2012 R2
|
Multi-master and Multi-drop
|
Master mode: 32 TCP slaves
Slave mode: 16 TCP masters (request queue 32-deep for each master)
|
Support
|
Smart Routing, Serial Redirection, ProCOM, Priority Control, MXview, SNMP v1 (read only)
|
• Physical Characteristics
|
Housing
|
Plastic, IP30
|
Weight
|
MGate MB3170: 360 g
MGate MB3270: 380 g
|
Dimensions
|
Without ears: 29 x 89.2 x 118.5 mm (1.14 x 3.51 x 4.67 in)
With ears extended: 29 x 89.2 x 124.5 mm (1.14 x 3.51 x 4.90 in)
|
• Environmental Limits
|
Operating Temperature
|
Standard Models: 0 to 60°C (32 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
|
Storage Temperature
|
-40 to 85°C (-40 to 185°F)
|
Ambient Relative Humidity
|
5 to 95% (non-condensing)
|
Altitude
|
Up to 2000 m (795 hPa), higher altitudes on demand
|
Note
|
Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
|
• Power Requirements
|
Input Voltage
|
12 to 48 VDC
|
Power Connector
|
Terminal block
|
Power Consumption
|
MB3170: 435 mA @ 12 V, 218 mA @ 24 V, 109 mA @ 48 V
MB3170I: 555 mA @ 12 V, 278 mA @ 24 V, 138 mA @ 48 V MB3270: 435 mA @ 12 V, 218 mA @ 24 V, 109 mA @ 48 V MB3270I: 510 mA @ 12 V, 255 mA @ 24 V, 128 mA @ 48 V
|
Relay Output
|
1 digital relay output to alarm (normal close): Current carrying capacity 1 A @ 30 VDC
|
• Standards and Certifications
|
Safety
|
UL 508, EN 60950-1*
|
Hazardous Location
|
UL/cUL Class 1 Division 2 Groups A/B/C/D,
ATEX Zone 2 Ex nA IIC T3 Gc, IECEx*
|
EMC
|
CE, FCC
|
EMI
|
EN 55022 Class A, FCC Part 15 Subpart B Class A
|
EMS
|
EN 55024
EN 61000-4-2 (ESD) Level 3 EN 61000-4-3 (RS) Level 3 EN 61000-4-4 (EFT) Level 4 EN 61000-4-5 (Surge) Level 3 EN 61000-4-6 (CS) Level 3 EN 61000-4-8 (PFMF) Level 1 EN 61000-4-11
|
Marine
|
DNV*
|
Shock
|
IEC 60068-2-27
|
Freefall
|
IEC 60068-2-32
|
Vibration
|
IEC 60068-2-6
|
• *Certification process is underway for fiber models. Please contact a Moxa sales representative for details.
|
• Reliability
|
MTBF (mean time between failures)
|
MGate MB3170: 210,794 hrs
MGate MB3270: 125,234 hrs
|
• Warranty
|
Warranty Period
|
5 years
|
Details
|
See www.moxa.com/warranty
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Features
- Accessible by up to 16 TCP master/client devices, or connect to up to 32 TCP slave/server devices
- Supports up to 31 or 62 serial slave devices
- Ethernet cascading for easy wiring
- Serial port routing by IP address, TCP port, or ID mapping
- Serial redirector function provided
- Embedded Modbus traffic monitor
- 10/100BaseTX (RJ45) or 100BaseFX (single mode or multi-mode with SC/ST connector)
|
|
|
|
|
|
|