The NDR Series of DIN rail power supplies is designed specifically for use in industrial applications. The 40 to 63 mm slim form-factor enables the power supplies to be easily installed in small and confined spaces such as cabinets. The broad operating temperature range of -20 to 70°C means they are capable of operating in harsh environments. The NDR Series has an AC input range from 90 VAC to 264 VAC, and conforms to the EN 61000-3-2 standard. In addition, these power supplies feature constant current mode to provide overload protection.
-
Wattage
NDR-120-24: 120 W
NDR-120-48: 120 W
NDR-240-48: 240 W
-
Voltage
NDR-120-24: 24 VDC
NDR-120-48: 48 VDC
NDR-240-48: 48 VDC
-
Current Rating
NDR-120-24: 0 to 5 A
NDR-120-48: 0 to 2.5 A
NDR-240-48: 0 to 5 A
-
Ripple and Noise
NDR-120-24: 120 mVp-p
NDR-120-48: 150 mVp-p
NDR-240-48: 150 mVp-p
-
Voltage Adjustment Range
NDR-120-24: 24 to 28 VDC
NDR-120-48: 48 to 55 VDC
NDR-240-48: 48 to 55 VDC
-
Setup/Rise Time at Full Load
NDR-120-24: 2500 ms, 60 ms at 115 VAC
NDR-120-24: 1200 ms, 60 ms at 230 VAC
NDR-120-48: 2500 ms, 60 ms at 115 VAC
NDR-120-48: 1200 ms, 60 ms at 230 VAC
NDR-240-48: 3000 ms, 100 ms at 115 VAC
NDR-240-48: 1500 ms, 100 ms at 230 VAC
-
Typical Hold Up Time at Full Load
NDR-120-24: 10 ms at 115 VAC
NDR-120-24: 16 ms at 230 VAC
NDR-120-48: 10 ms at 115 VAC
NDR-120-48: 16 ms at 230 VAC
NDR-240-48: 22 ms at 115 VAC
NDR-240-48: 28 ms at 230 VAC
-
Typical Efficiency
NDR-120-24: 88%
NDR-120-48: 89%
NDR-240-48: 90%
-
Typical Current
NDR-120-24: 1.3 A @ 230 VAC, 2.25 A @ 115 VAC
NDR-120-48: 1.3 A @ 230 VAC, 2.25 A @ 115 VAC
NDR-240-48: 1.3 A @ 230 VAC, 2.5 A @ 115 VAC
-
Voltage Range
90 to 264 VAC (47 to 63 Hz)
127 to 370 VDC
-
Inrush Current (cold start)
35 A @ 230 VAC, 20 A @ 115 VAC
-
Rated Output Power
-
Protection Type
Constant current limiting, recovers automatically after fault condition is removed
-
Over-Voltage Range
NDR-120-24: 29 to 33 V
NDR-120-48: 56 to 65 V
NDR-240-48: 56 to 65 V
-
Protection Type
Shut down operating voltage, repower on to recover
-
Safety
UL 508, EN 62368-1, IEC 62368-1
-
EMC
EN 55032/24, EN 61000-3-2 Class A, EN 61000-3-3
-
EMS
IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m
IEC 61000-4-4 EFT: Power: 2 kV
IEC 61000-4-5 Surge: Power: 2 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8 PFMF
IEC 61000-4-11 DIPs
-
Dimensions
NDR-120-24: 123.75 x 125.20 x 40 mm (4.87 x 4.93 x 1.57 in)
NDR-120-48: 123.75 x 125.20 x 40 mm (4.87 x 4.93 x 1.57 in)
NDR-240-48: 127.81 x 123.75 x 63 mm (5.03 x 4.87 x 2.48 in)
-
Weight
NDR-120-24: 500 g (1.10 lb)
NDR-120-48: 500 g (1.10 lb)
NDR-240-48: 900 g (1.98 lb)
-
Operating Temperature
-20 to 70°C (-4 to 158°F)
-
Storage Temperature
-40 to 85°C (-40 to 185°F)
-
Ambient Relative Humidity
20 to 95% (non-condensing)
-
Max. Operating Temperature at Full Load
NDR-120-48: 45°C (113°F)
NDR-120-24: 45°C (113°F)
NDR-240-48: 50°C (122°F)
-
Standards
-
Time
NDR-120-24: 453,334 hrs
NDR-120-48: 453,334 hrs
NDR-240-48: 230,206 hrs
|
|
|
|
|
|
|
|
|
|
|
|
|
Features
- DIN-rail mounted power supply
- Slim form factor that is ideal for cabinet installation
- Universal AC power input
- High power conversion efficiency
|
|
|
|
|
|
|