Environmental Product Compliance
|
China RoHS
|
Environmentally Friendly Use Period = 25;
|
General
|
Net weight
|
2 kg
|
Efficiency
|
> 91 % (With 600 V DC and nominal values)
|
Insulation voltage input/output
|
4 kV AC (type test)
|
|
2 kV AC (routine test)
|
Insulation voltage input / PE
|
2 kV AC (type test)
|
|
2 kV AC (routine test)
|
Insulation voltage output / PE
|
500 V DC (routine test)
|
Protection class
|
I (with PE connection)
|
Degree of protection
|
IP20
|
MTBF (IEC 61709, SN 29500)
|
|
|
> 701000 h (40 °C)
|
Mounting position
|
horizontal DIN rail NS 35, EN 60715
|
Assembly instructions
|
alignable: horizontally 0 mm, vertically 50 mm
|
Standards and Regulations
|
Electromagnetic compatibility
|
Conformance with EMC Directive 2014/30/EU
|
Noise immunity
|
EN 61000-6-2:2005
|
Connection in acc. with standard
|
CUL
|
Standards/regulations
|
EN 61000-4-2
|
Contact discharge
|
4 kV (Test Level 2)
|
Standards/regulations
|
EN 61000-4-3
|
Frequency range
|
80 MHz ... 3 GHz
|
Test field strength
|
10 V/m
|
Frequency range
|
1.4 GHz ... 2 GHz
|
Test field strength
|
3 V/m
|
Standards/regulations
|
EN 61000-4-4
|
Comments
|
Criterion B
|
Standards/regulations
|
EN 61000-6-3
|
|
EN 61000-4-6
|
Frequency range
|
150 kHz ... 80 MHz
|
Voltage
|
10 V (Test Level 3)
|
Standards/regulations
|
EN 61000-4-11
|
Low Voltage Directive
|
Conformance with LV directive 2006/95/EC
|
Standard - Electrical safety
|
EN 60950-1/VDE 0805 (SELV)
|
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
|
EN 50178/VDE 0160 (PELV)
|
Standard – Safety extra-low voltage
|
EN 60950-1 (SELV)
|
|
EN 60204 (PELV)
|
Standard - Safe isolation
|
DIN VDE 0100-410
|
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment
|
EN 50178
|
Standard – Limitation of mains harmonic currents
|
EN 61000-3-2
|
UL approvals
|
UL/C-UL listed UL 508
|
|
UL/C-UL Recognized UL 60950-1
|
Shock
|
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
|
Vibration (operation)
|
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
|
|
15 Hz ... 150 Hz, 2.3g, 90 min.
|
Rail applications
|
EN 50121-4
|
Connection data, input
|
Connection method
|
Screw connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
2.5 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
Conductor cross section AWG min.
|
24
|
Conductor cross section AWG max.
|
14
|
Stripping length
|
9 mm
|
Screw thread
|
M2,5
|
Output data
|
Nominal output voltage
|
24 V DC ±1 %
|
Setting range of the output voltage (U
Set)
|
22.5 V DC ... 29.5 V DC (U
IN > 475 V DC)
|
|
22.5 V DC ... 28 V DC (U
IN ≤ 475 V DC)
|
Nominal output current (I
N)
|
20 A (-25 °C ... 55 °C)
|
Derating
|
55 °C ... 70 °C (2.5%/K)
|
Connection in parallel
|
Yes, for redundancy and increased capacity
|
Connection in series
|
yes
|
Feedback resistance
|
35 V DC
|
Protection against surge voltage on the output
|
Yes, < 35 V DC
|
Max. capacitive load
|
Unlimited
|
Active current limitation
|
Approx. 25 A (for short-circuit)
|
Control deviation
|
< 1 % (change in load, static 10 % ... 90 %)
|
|
< 2 % (change in load, dynamic 10 % ... 90 %)
|
|
< 0.1 % (change in input voltage ±10 %)
|
Residual ripple
|
< 40 mV
PP
|
Output power
|
480 W
|
Typical response time
|
< 1 s
|
Peak switching voltages nominal load
|
< 10 mV
PP
|
Maximum power dissipation in no-load condition
|
3.8 W
|
Power loss nominal load max.
|
45 W
|
Dimensions
|
Width
|
115 mm
|
Height
|
130 mm
|
Depth
|
152.5 mm
|
Weight per piece
|
1780.0 GRM
|
Input data
|
Nominal input voltage range
|
600 V DC
|
Input voltage range
|
450 V DC ... 840 V DC (Dielectric strength up to 900 V DC)
|
Frequency range DC
|
0 Hz
|
Discharge current to PE
|
< 3.5 mA
|
Current consumption
|
0.9 A (600 V DC)
|
Nominal power consumption
|
527.3 VA
|
Inrush surge current
|
< 26 A
|
Mains buffering
|
typ. 15 ms (600 V DC)
|
Choice of suitable circuit breakers
|
4 A ... 6 A (1000 V DC)
|
Power factor (cos phi)
|
1
|
Type of protection
|
Transient surge protection
|
Protective circuit/component
|
Varistor
|
Connection data, onput
|
Connection method
|
Screw connection
|
Conductor cross section solid min.
|
0.5 mm²
|
Conductor cross section solid max.
|
6 mm²
|
Conductor cross section flexible min.
|
0.5 mm²
|
Conductor cross section flexible max.
|
4 mm²
|
Conductor cross section AWG min.
|
12
|
Conductor cross section AWG max.
|
10
|
Stripping length
|
14 mm
|
Screw thread
|
M3
|
Ambient conditions
|
Degree of protection
|
IP20
|
Ambient temperature (operation)
|
-25 °C ... 70 °C (> 55° C derating : 2.5%/K)
|
Ambient temperature (storage/transport)
|
-40 °C ... 85 °C
|
Max. permissible relative humidity (operation)
|
≤ 95 % (at 25 °C, non-condensing)
|
Climatic class
|
3K3 (in acc. with EN 60721)
|
Degree of pollution
|
2
|
Approvals
|
|
- cULus Listed
- cULus Recognized
- EAC
- UL Recognized
- cUL Recognized
- cUL Listed
- UL Listed
|